| 1.5 mm² | Class 1Class 2Class 5 | Solid, stranded rigid, or flexible copper conductor | 1.5 mm² lug | Confirm the barrel accepts the actual conductor diameter and insulation strip length. | Ø4.3–Ø5.3 mm | M4 or M5 | Suitable for small control, instrumentation, and auxiliary power conductors. |
| 2.5 mm² | Class 1Class 2Class 5 | Solid, stranded rigid, or flexible copper conductor | 2.5 mm² lug | Flexible Class 5 conductors may require a flexible-conductor-compatible barrel. | Ø5.3–Ø6.4 mm | M5 or M6 | Common for branch circuits and control wiring. |
| 4 mm² | Class 1Class 2Class 5 | Solid, stranded rigid, or flexible copper conductor | 4 mm² lug | Do not select only by insulation outside diameter; verify the stripped conductor fits the barrel. | Ø5.3–Ø6.4 mm | M5 or M6 | Often used in compact distribution and equipment wiring. |
| 6 mm² | Class 1Class 2Class 5 | Solid, stranded rigid, or flexible copper conductor | 6 mm² lug | Use the lug’s specified crimp range and the correct die for the conductor and lug material. | Ø6.4–Ø8.4 mm | M6 or M8 | Common for feeder, battery, and equipment termination points. |
| 10 mm² | Class 1Class 2Class 5 | Solid, stranded rigid, or flexible copper conductor | 10 mm² lug | Check conductor strand formation, barrel length, and required crimp positions. | Ø6.4–Ø8.4 mm | M6 or M8 | Suitable for medium-current power and earthing connections. |
| 16 mm² | Class 2Class 5Class 6 | Stranded rigid, flexible, or very flexible conductor | 16 mm² lug | Class 5 and Class 6 conductors can have different strand layouts; verify the approved barrel range. | Ø8.4–Ø10.5 mm | M8 or M10 | Used for larger equipment feeds, bonding, and battery connections. |
| 25 mm² | Class 2Class 5Class 6 | Stranded rigid, flexible, or very flexible conductor | 25 mm² lug | Check whether the selected lug is rated for compact, sector-shaped, or circular conductors. | Ø8.4–Ø10.5 mm | M8 or M10 | Typical for distribution panels and medium-duty power circuits. |
| 35 mm² | Class 2Class 5Class 6 | Stranded rigid, flexible, or very flexible conductor | 35 mm² lug | Match both the conductor cross-section and the actual barrel internal diameter. | Ø10.5–Ø13.0 mm | M10 or M12 | Suitable for larger feeders, switchgear, and grounding conductors. |
| 50 mm² | Class 2Class 5Class 6 | Stranded rigid, flexible, or very flexible conductor | 50 mm² lug | For flexible conductors, use a barrel designed to prevent strand splaying during crimping. | Ø10.5–Ø13.0 mm | M10 or M12 | Common in industrial distribution and high-current equipment. |
| 70 mm² | Class 2Class 5Class 6 | Stranded rigid, flexible, or very flexible conductor | 70 mm² lug | Verify crimp-tool capacity, barrel wall thickness, and available installation clearance. | Ø13.0–Ø17.0 mm | M12 or M16 | Used for high-current feeders, switchboards, and power conversion equipment. |
| 95 mm² | Class 2Class 5Class 6 | Stranded rigid, flexible, or very flexible conductor | 95 mm² lug | Confirm the conductor’s actual outside diameter and the lug’s approved conductor range. | Ø13.0–Ø17.0 mm | M12 or M16 | Suitable for major distribution, transformer, and industrial power connections. |
| 120 mm² | Class 2Class 5Class 6 | Stranded rigid, flexible, or very flexible conductor | 120 mm² lug | Use a lug and crimp system qualified for the conductor class and installation environment. | Ø13.0–Ø17.0 mm | M12 or M16 | Typically used in high-capacity feeders and switchgear assemblies. |
| 150 mm² | Class 2Class 5Class 6 | Stranded rigid, flexible, or very flexible conductor | 150 mm² lug | Check whether the palm width and hole position fit the equipment terminal. | Ø17.0 mm | M16 | For high-current industrial, utility, and power distribution applications. |
| 185 mm² | Class 2Class 5Class 6 | Stranded rigid, flexible, or very flexible conductor | 185 mm² lug | Check the required number of crimps, tooling range, and minimum bending radius. | Ø17.0 mm | M16 | Used for large feeders, busbar connections, and high-power equipment. |
| 240 mm² | Class 2Class 5Class 6 | Stranded rigid, flexible, or very flexible conductor | 240 mm² lug | For parallel cables, verify phase spacing, palm orientation, and terminal loading. | Ø17.0 mm | M16 | Suitable for high-capacity switchgear, transformers, and industrial feeders. |