| Tank Function | Fire-water storage, process-water buffer, utility-water storage, emergency reserve, or treated-water storage. | Define whether the tank is purely passive or includes powered equipment such as mixers, level instruments, heaters, pumps, valves, or ventilation devices. | ATEX Directive 2014/34/EU may apply to equipment and protective systems intended for potentially explosive atmospheres. | Approved process description, equipment list, and hazardous-area classification drawing. |
| Hazardous Gas Zone | Zone 0: explosive gas atmosphere is present continuously, for long periods, or frequently. Zone 1: likely during normal operation. Zone 2: not likely during normal operation and, if it occurs, exists only briefly. | Use equipment suitable for the actual zone and for the gas group and temperature class specified by the site classification. | EN IEC 60079-10-1 for gas-area classification; EN IEC 60079-14 for electrical installation design and selection. | Zone classification report, hazardous-area plot plan, gas group, and temperature-class requirements. |
| ATEX Gas Equipment Category | Zone 0 normally requires Category 1G; Zone 1 normally requires Category 2G or higher protection; Zone 2 normally requires Category 3G or higher protection. | Select the category based on the zone, while also checking the equipment protection level, protection concept, gas group, and temperature class. | ATEX 2014/34/EU; equipment marking commonly includes categories such as 1G, 2G, or 3G. | EU Declaration of Conformity, certificate information where applicable, and complete equipment marking. |
| Hazardous Dust Zone | Zone 20: combustible dust cloud is present continuously, for long periods, or frequently. Zone 21: likely during normal operation. Zone 22: not likely during normal operation and, if it occurs, exists only briefly. | For dust areas, evaluate dust layers, dust-cloud ignition risk, enclosure protection, surface temperature, and cleaning methods. | EN IEC 60079-10-2 for dust-area classification; EN IEC 60079-14 for installation requirements. | Dust classification report, minimum ignition temperature data, dust group information, and housekeeping procedures. |
| ATEX Dust Equipment Category | Zone 20 normally requires Category 1D; Zone 21 normally requires Category 2D or higher protection; Zone 22 normally requires Category 3D or higher protection. | Confirm that electrical and mechanical accessories are suitable for the identified dust zone and for conductive or non-conductive dust where relevant. | ATEX 2014/34/EU; marking commonly includes categories such as 1D, 2D, or 3D. | Dust-zone compliance documents, equipment marking, and installation inspection records. |
| Equipment Protection Level | Gas: Ga, Gb, or Gc. Dust: Da, Db, or Dc. The required level depends on the probability and duration of the explosive atmosphere. | Match the protection level to the zone: Ga/Da for the highest protection requirement, followed by Gb/Db and Gc/Dc for lower-risk zones. | EN IEC 60079-0 and the applicable protection-concept standards in the EN IEC 60079 series. | Verify EPL on the nameplate, certificate, technical file, and project hazardous-area schedule. |
| Gas Group and Temperature Class | Common gas groups include IIA, IIB, and IIC. Temperature classes range from T1 to T6, with T6 imposing the lowest maximum surface-temperature limit. | The selected equipment must be rated for the identified gas group and have a maximum surface temperature below the ignition temperature of the gas or vapor. | EN IEC 60079-0; the final requirement is established by the site hazardous-area study and process safety documentation. | Gas or vapor safety data, temperature-class schedule, and equipment nameplate review. |
| Tank Construction Material | Carbon steel, stainless steel, coated steel, or engineered polymer systems may be used depending on water chemistry, structural loads, and operating conditions. | Select materials based on corrosion allowance, chloride level, pH, temperature, UV exposure, fire-water requirements, and compatibility with stored water. | Project material specifications, applicable structural codes, and water-contact requirements defined by the destination market. | Material certificates, coating system data, weld procedures, corrosion assessment, and lining compatibility statement. |
| Static Electricity and Bonding | Potential electrostatic charging may occur on insulated tank surfaces, coatings, plastic components, flexible hoses, or non-conductive accessories. | Provide equipotential bonding and earthing where required. Avoid unverified insulating materials in classified areas. | EN IEC 60079-14 and IEC 60079-32-1 provide guidance on electrostatic hazards and control measures. | Earthing design, continuity test results, bonding layout, and inspection records. |
| Instrumentation and Controls | Typical devices include level transmitters, high-level switches, temperature sensors, pressure indicators, flow meters, and remote monitoring units. | Use suitably certified equipment or locate non-ATEX equipment outside the classified area with appropriate isolation and installation controls. | EN IEC 60079-11 for intrinsically safe apparatus; EN IEC 60079-25 for intrinsically safe systems. | Instrument certificates, loop diagrams, entity parameters, cable-gland data, and inspection schedule. |
| Pumps, Mixers, and Motors | Rotating equipment may introduce ignition sources through electrical faults, hot surfaces, friction, bearings, mechanical seals, or static discharge. | Specify hazardous-area certification, motor protection, temperature monitoring, seal arrangement, and maintenance requirements for each item. | EN IEC 60079 series; mechanical equipment may also require assessment under ATEX depending on its ignition-risk potential. | Certificates, ignition-hazard assessment, motor data sheets, protection settings, and maintenance instructions. |
| Ventilation and Breathing System | Atmospheric tanks may require screened vents, pressure-vacuum protection, flame-arresting devices, or controlled ventilation depending on the stored liquid and surrounding process. | Evaluate whether vapors can accumulate inside or around the tank. Vent outlets should be located to prevent hazardous vapor collection near ignition sources. | Project process-safety requirements, EN IEC 60079-10-1, and applicable tank design standards. | Vent sizing calculation, vapor assessment, relief-device specification, and hazardous-location review. |
| Capacity and Hydraulics | Capacity is determined by demand rate, required reserve duration, refill time, fire-water demand, process variability, and emergency operating philosophy. | Calculate usable volume rather than gross volume, allowing for dead volume, freeboard, sediment allowance, thermal expansion, and required emergency reserve. | Project hydraulic calculations and the applicable local or international tank design standard. | Design basis, hydraulic profile, flow-demand calculation, refill analysis, and nozzle schedule. |
| Climate and Environmental Conditions | Temperature, altitude, humidity, solar radiation, wind, snow, seismic activity, salt spray, flooding, and corrosive atmospheres vary significantly by project location. | Design the shell, foundation, coatings, insulation, instrumentation, and electrical enclosures for the complete site environmental range. | IEC 60529 for enclosure ingress protection where applicable; structural and environmental requirements are project-specific. | Site environmental data, wind and seismic parameters, coating specification, and enclosure IP assessment. |
| Fire and Emergency Requirements | Fire-water tanks may require dedicated volume, reliable suction conditions, automatic refill, low-level alarms, and separation from process hazards. | Do not reduce emergency reserve because of normal process consumption. Confirm independent availability, access, and inspection provisions. | Applicable fire-protection rules, authority requirements, and project fire-water philosophy. | Fire-water demand calculation, emergency operating procedure, alarm matrix, and authority approval records. |
| Installation and Maintenance | Access platforms, ladders, inspection openings, drainage, cleaning points, spare parts, and safe isolation may be required. | Ensure maintenance activities do not introduce ignition sources. Define inspection intervals for ATEX equipment and bonding systems. | EN IEC 60079-17 covers inspection and maintenance of electrical installations in explosive atmospheres. | Maintenance manual, inspection checklist, permit-to-work requirements, spare-parts list, and training records. |
| Global Compliance and Documentation | Projects outside the European Union may require local certification, statutory inspection, electrical approvals, pressure-equipment review, or authority-specific documentation. | Separate mandatory legal requirements from voluntary design standards. Confirm the governing law before procurement. | ATEX requirements apply within their legal scope; IECEx and local regulations may be required for other jurisdictions. | Compliance matrix, certificates, drawings, calculations, inspection and test plans, manuals, and final documentation dossier. |